Climate Pro X14

Electronic
Features
Control Panel
Thermostat Control
Programmable
Electronic
Rating Conditions: 95°F @ 60% RH
13,200 Btu/h
Cooling Capacity
Voltage Requirement
1 Phase, 115v
Electrical
Characteristics
Total Power Consumption
1.3 kW
Current Consumption
11.5 amps
Recommended Fuse Size
15 amps
NEMA Plug Configuration
5 – 15P
Min. – Max. Voltage
104 – 127v
Fans
Motor Output
0.23 kW
Fan Type
Centrifugal
Evaporator
Max. Air Flow – High/Mid/Low
440/410/385 CFM
Max. External Static Pressure
0.31 IWG
Fan Type
Centrifugal
Condensor
Max. Air Flow – High/Mid/Low
830/770/720 CFM
Max. External Static Pressure
0.19 IWG
Compressor
Type
Hermetic Rotary
Output
0.75 kW
Refrigerant
Type
R-410A
Dimensions
W x D X H
22 x 29 x 48 in
Net Weight/
Shipping Weight
181/218 lb
Power Cord
Gauge
14AWG (3-core)
Length
10 ft
Condensate Tank Capacity
5 gal
Operating Condition
Min. – Max (@ 50% RH)
Cooling: 70°F – 113°F
Max. Duct Length
Per Cold Duct Hose
30 ft
Exhaust Duct Hose
60 ft
Max. Sound Level
With Exhaust Duct – High/Mid /Low
61/60/59 dB(A)
Without Exhaust Duct – High/ Mid/Low
62/61/60 dB(A)
All specification subject to change without notice.