top of page
iStock-179027144_wr.jpg

Climate Pro X14

X14_Left_Shadow.png
Electronic
Features

Control Panel

Thermostat Control

Programmable

Electronic

Rating Conditions: 95°F @ 60% RH

13,200 Btu/h

Cooling Capacity

Voltage Requirement

1 Phase, 115v

Electrical 
Characteristics

Total Power Consumption

1.3 kW

Current Consumption

11.5 amps

Recommended Fuse Size

15 amps

NEMA Plug Configuration

5 – 15P

Min. – Max. Voltage

104 – 127v

Fans

Motor Output 

0.23 kW

Fan Type

Centrifugal

Evaporator

Max. Air Flow – High/Mid/Low

440/410/385 CFM

Max. External Static Pressure

0.31 IWG

Fan Type

Centrifugal

Condensor

Max. Air Flow – High/Mid/Low

830/770/720 CFM

Max. External Static Pressure

0.19 IWG

Compressor

Type

Hermetic Rotary

Output

0.75 kW

Refrigerant

Type

R-410A

Dimensions

W x D X H

22 x 29 x 48 in

Net Weight/
Shipping Weight

181/218 lb

Power Cord

Gauge

14AWG (3-core)

Length

10 ft

Condensate Tank Capacity

5 gal

Operating Condition

Min. – Max (@ 50% RH)

Cooling: 70°F – 113°F

Max. Duct Length

Per Cold Duct Hose

30 ft

Exhaust Duct Hose

60 ft

Max. Sound Level

With Exhaust Duct – High/Mid /Low

61/60/59 dB(A)

Without Exhaust Duct – High/ Mid/Low

62/61/60 dB(A)

All specification subject to change without notice.