Electronic
Features

Control

Programmable

15,700 Btu/h
10,800 Btu/h

Cooling Capacity
Air: 80°F at
50% RH
Water
(EWT/LWT):
85°F/95°F

Total cooling capacity
Sensible cooling capacity

Electrical 
Characteristics

Voltage Requirement

1 Phase, 115V

Total Power Consumption

1.27 kW

Current Consumption

11.7 amps

Recommended Fuse Size

15 amps

NEMA Plug Configuration

5-15

Min. – Max. Voltage

105 – 125

ERR
Fans

Motor Output – high/mid/low

12.3

0.11/0.08 kW

Evaporator

Fan Type

Centrifugal

Max. Air Flow – high/mid/low

565/540 CFM

Max. External Static Pressure

0.31 IWG

Condenser

 Water Cool Condenser (4.8 GPM min)

Compressor

Type

Hermetic Rotary

Output

1.16 kW

Refrigerant

Type

R-410A

Dimensions

W x D X H

21 x 27 x 41.5 in

Net Weight/
Shipping Weight

178/209 lb

Power Cord

Gauge/Length

12 AWG (3-core)/6 ft

Condensate Tank Capacity

5 gal

 Auto Pump Included

Operating Condition

Min. – Max (@ 50% RH)

65° – 95°F
40° – 90°F (Condenser Water)

Max. Equivalent Duct Length

Per Cold Duct Hose

25 ft

Max. Sound Level

Without Condenser – Duct high/low

62/60 dB(A)

Water Pressure

Min.

12 psi

Water Valve Connection

Inlet/Outlet

1/2° NPT Female

All specification subject to change without notice.

OUTSTANDING REPUTATION 

QUALITY EQUIPMENT

DEPENDABLE SERVICE

PROTECT YOUR
PROJECT OR FACILITY  

Contact us today for a free quote, and learn how affordable it can be to rent or buy the temporary climate solution your company needs.

Rankin logo-03.png

CONTACT

 
1958 Brandon Court | Glendale Heights, IL 60139
4009 Lindbergh Dr. | Addison, Dallas County, TX 75001
 
Toll Free: 800.966.7100
 
Phone: 630.620.1300
 
Fax: 630.620.7810
  • Facebook - White Circle
  • LinkedIn - White Circle

© 2020 Rankin Group. All Rights Reserved.