iStock-179027144_wr.jpg

Climate Pro K60

Electronic
Features

Control Panel

Programmable

Rating Conditions: 95°F @ 60% RH

60,000 Btu/h

Cooling Capacity

Voltage Requirement

1 Phase, 208/230v

Electrical 
Characteristics

Total Power Consumption

6.6 kW

Current Consumption

31.5 amps*

Recommended Fuse Size

50 amps

NEMA Plug Configuration

6 – 50

Min. – Max. Voltage

198 – 253v

Fans

Motor Output 

0.56 kW Evaporator

0.30 kW x 2 Condensers 

Fan Type

Centrifugal

Evaporator

Max. Air Flow – High/Mid/Low

1770/1710/1650 CFM

Max. External Static Pressure

0.9 IWG

Fan Type

Centrifugal

Condensor

Max. Air Flow – High/Mid/Low

2400 CFM

Max. External Static Pressure

0.85 IWG

Compressor

Type

Hermetic Rotary

Output

3.45 kW

Refrigerant

Type

R-410A

Dimensions

W x D X H

31 x 55 x 64 in

Net Weight/
Shipping Weight

582  / 666 lb

Power Cord

Gauge

6 AWG (3-core)

Length

6 ft

Condensate Tank Capacity

5 gal

Operating Condition

Min. – Max (@ 50% RH)

Cooling: 65°F – 105°F

Max. Duct Length

Per Cold Duct Hose

40 ft

Exhaust Duct Hose

100 ft

Max. Sound Level

With Exhaust Duct – High/Mid /Low

69/68/67 dB(A)

Without Exhaust Duct – High/ Mid/Low

71/70/69 dB(A)

*Specification information shown with 230 V.

All specification subject to change without notice.

OUTSTANDING REPUTATION 

QUALITY EQUIPMENT

DEPENDABLE SERVICE

PROTECT YOUR
PROJECT OR FACILITY  

Contact us today for a free quote, and learn how affordable it can be to rent or buy the temporary climate solution your company needs.

Rankin logo-03.png

CONTACT

 
1958 Brandon Court | Glendale Heights, IL 60139
4009 Lindbergh Dr. | Addison, Dallas County, TX 75001
 
Toll Free: 800.966.7100
 
Phone: 630.620.1300
 
Fax: 630.620.7810
  • Facebook - White Circle
  • LinkedIn - White Circle

© 2020 Rankin Group. All Rights Reserved.