iStock-179027144_wr.jpg

Climate Pro K24

Electronic
Features

Control Panel

Programmable

Rating Conditions: 95°F @ 60% RH

24,000 Btu/h

Cooling Capacity

Voltage Requirement

1 Phase, 208-230 V

Electrical 
Characteristics

Total Power Consumption

2.9 kW*

Current Consumption

12.5 amps*

Recommended Fuse Size

20 amps

NEMA Plug Configuration

6-20

Min. – Max. Voltage

198 – 253 V

Fans

Motor Output 

0.56 kW*

Fan Type

Centrifugal

Evaporator

Max. Air Flow – High/Mid/Low

650/600/530 CFM*

Max. External Static Pressure

0.5 IWG

Fan Type

Centrifugal

Condensor

Max. Air Flow – High/Mid/Low

870/760/740 CFM

Max. External Static Pressure

0.16 IWG

Compressor

Type

Hermetic Rotary

Output

1.5 kW

Refrigerant

Type

R-410A

Dimensions

W x D X H

22 x 27 x 51 in

Net Weight/
Shipping Weight

205  / 243 lb

Power Cord

Gauge

12 AWG (3-core)

Length

6 ft

Condensate Tank Capacity

5 gal

Operating Condition

Min. – Max (@ 50% RH)

65°F – 95°F

Max. Duct Length

Per Cold Duct Hose

50 ft

Exhaust Duct Hose

45 ft

Max. Sound Level

With Condenser Duct – High/Mid /Low

66/64/61 dB(A)

Without Condenser Duct – High/ Mid/Low

68/66/63 dB(A)

*Specification information shown with 230V

All specification subject to change without notice.

OUTSTANDING REPUTATION 

QUALITY EQUIPMENT

DEPENDABLE SERVICE

PROTECT YOUR
PROJECT OR FACILITY  

Contact us today for a free quote, and learn how affordable it can be to rent or buy the temporary climate solution your company needs.

Rankin logo-03.png

CONTACT

 
1958 Brandon Court | Glendale Heights, IL 60139
4009 Lindbergh Dr. | Addison, Dallas County, TX 75001
 
Toll Free: 800.966.7100
 
Phone: 630.620.1300
 
Fax: 630.620.7810
  • Facebook - White Circle
  • LinkedIn - White Circle

© 2020 Rankin Group. All Rights Reserved.