MovinCool_CMW30.jpg
Electronic
Features

Operation
Control

Wall Mounted Controller
Programmable

Electrical 
Characteristics

Voltage Requirement

1 Phase, 208/230V

Recommended Fuse Size

20 amps

Min. – Max. Voltage

198 – 250

Cooling Capacity and Power Consumption

Evaporator: 80°F, 50% RH

Condenser: EWT/LWT: 85°F/95°F

Total Cooling Capacity

 29,400 Btu/h1

Sensible Cooling Capacity

20,800 Btu/h1

Power Consumption

1.99 kW1

Current Consumption

8.9 amps1

Evaporator: 72°F, 50% RH

Condenser: EWT/LWT: 85°F/95°F

Total Cooling Capacity

 25,200 Btu/h1

Sensible Cooling Capacity

22,000 Btu/h1

Power Consumption

2.00 kW1

Current Consumption

9 amps1

IERR

17.0

Evaporator

Fan Type

Centrifugal1

Max. Air Flow – high/mid/low

1060/840 CFM

Max. External Static Pressure

0.66 IWG

Compressor

Type

Hermetic Swing Inverter

Refrigerant

Type

R-410A

Dimensions

W x D x H (without flange)

45 x 32 x 20 in

W x D x H (with flange)

49 x 35 x 20 in

Net Weight/
Shipping Weight

236/271 lb

Condensate Tank Capacity

Pump Rate

Head

5 gal/h

 4 ft

Operating Condition

Evaporator

55°F – 95°F, 50% RH

Condenser

 45°F – 115°F (Condenser Water)

Maximum Duct Length

Per Cold Duct Hose

120 ft2

Hot Duct Hose

N/A

Maximum Sound Level

Under Ceiling Title with Evaporator Duct

55 dB(A)

All specification subject to change without notice.